Acme Model S7000L Automatic Liquid Cylinder Gas Changeover Manifolds are designed to eliminate system downtime by ensuring uninterrupted gas flow from two banks of cryogenic liquid gas cylinders. Model S7000L manifolds are identical in function and performance to Model SLIQ manifolds, however, they are panel mounted instead of enclosed, and do not contain status indicating lights. High and low pressure models are available.

The changeover regulator incorporates two regulators within a common body and a single outlet. The design is such that with different set pressures, only one liquid cylinder bank can be discharged at a time. The units line regulator provides downstream adjustment for final pressure delivery. It features a Gas Saver Circuit, which contains check valves, set just below the cylinder relief valve setting to allow boil off on the reserve bank to be utilized, rather than wasted.||Once liquid cylinders have been installed, the changeover manifold will first accept flow from the pre-determined primary bank. The S7000Ls control knob points to the primary bank for easy identification. When the primary bank reaches a preset low pressure, the reserve bank automatically takes over. To replace the empty liquid cylinder bank, the operator simply turns the control knob to switch priority.

Markets
Applications
Connections Outlet: 3/8 Tube Compression Fitting
Dimensions 14″H x 12″W (Other sized available.
Inlet Pressure 350 PSIG (max)
Outlet Pressure High Pressure Unit: 175 PSIG|Low Pressure Unit: 75 PSIG
Gauges Brass: 2 1/2|Stainless Steel: 2
Instrument Air 90 PSIG
Material Components: Brass or Stainless Steel|Seats and Seals: Teflon|Panel: Steel Powder Coated White
# of Cylinders 2
Optional Equipment Acme Model S504 Indicating Pressure Switch (IPS)|Acme Model S300 Remote Alarm Box (alarm, lights and cable)|Floor Stand
Options Brass or Stainless Steel|Cylinders- 2,4,6,8,10,12,14,16|Alarm Options- Explosion proof and none |
Product Type Specialty Gas Manifold
PublishedDate 1770098038884
Required Power Supply 110 VAC
SEO Title S7000Ls2A-El580 | Gas Handling Liquid Transfer Systems | Manifolds
System Operations Once cylinders have been installed, the changeover manifold will first accept flow from the pre-determined primary bank. The S7000’s control knob points to the primary bank for easy identification.||When the primary bank reaches a preset low pressure, the reserve bank automatically takes over. To replace the empty cylinder bank, the operator simply turns the control knob to switch priority.